🔧 Configuration:

•   apcupsd is installed and running ✅
•   UPS (Smart-UPS 1500) detected and reporting via USB ✅
•   /etc/apcupsd/apcupsd.conf includes:
•   ONBATTERYDELAY 6
•   TIMEOUT 600 (shutdown after 10 min on battery)
•   BATTERYLEVEL, MINUTES also correctly defined ✅

⚡ Simulated Tests:

•   Manual onbattery trigger tested ✅
•   wall terminal alerts confirmed working ✅
•   msmtp email integration now fixed (no -s error) ✅

🧪 Shutdown flow:

•   apccontrol runs doshutdown, which calls:

/sbin/shutdown -h now apcupsd UPS forced shutdown”

✅ The correct command for Proxmox to shut down cleanly.

✅ Final Summary: Yes, Proxmox Will Shut Down Automatically

If the UPS:

•   loses mains power and
•   stays on battery for >10 minutes (or any other threshold we set)

→ Proxmox will shut itself down safely, thanks to apcupsd.